BLK SERIES Water chiller
--------FF Series--------
2FF|5FF|8FF
12FF|18FF|25FF
36FF|48FF
--------YF Series--------
0.5YF|1YF|2YF
5YF|8YF
--------YS Series--------
5YS|8YS
12YS|25YS
ZHY-401B|ZHY-601B
ZHM-1A|ZHM-1B|ZHM-1T
ZHM-1V|ZHM-1-250
Comp. Gas high(High
pressure≥3.0MPa)
1. Refrigerating System is blocked.
2. Refrigerant content is excessive.
3. Condenser is dirty.
4. Current of cooling water is small
5. Fan does not work
6. No cooling water
1. Replace filter-dryer
2. Reduce refrigerant
3. Clear up condenser?
4. Clear up filter of cooling
water
5. Replace fan or capacity.
6. Cooling water supply
1. Lack of refrigerant
2. Block of refrigeration system
3. Thermostat is faulty
4. PT-100 is faulty
5. The condenser is dirty.
6. Current of cooling water is small
7. Contactor does not work
8. Contactor is faulty
9. Exhaust fan does not work
1. Check the refrigeration system,
and filling the refrigerant
2. Replace filter-dryer
3. Confirm the parameter of the
thermostat is in consistent with
this user manual
4. Replace the platinum resistor
5. Clean the condenser
6. Clear up filter of cooling
7. Check the control circuit of
the contactor
8. Replace the AC contactor
9. Pressure-control switch fault
Or replace the fan motor or fan
capacitor
10. Replace the compressor or the
capacitor of the compressor.
Big deviation of
water temperature
Solenoid valve or electric control
trouble
Replace solenoid valve or electric
control parts
Too large of water
temperature
deviation
fault
Replace the solenoid valve or
electric control element
Thermostat LED no
light
Thermostat is faulty or F1 (0.5A) is
faulty
Replace the thermostat or F1
(0.5A)
1. F2 (10A) fuse is broken
2. Shaft of the pump is adhered to
the water seal
3. The control of the pump has
problem
4. Fault of capacitor of water pump
1. Replace the F2 (10A)
2. Rotate the pump shaft in
clockwise by the minus screwdriver
3. Check the control loop of the
water pump
4. Replace the capacitor of the